All DC i-PAM V-PAM
Indoor Unit :
ARXG36KMLA
Outdoor Unit :
AOHG36KRTA
Download :
Catalogues

Features

  • Slim and compact design
  • Easy maintenance
  • Drain pipe can be installed on either the left or right side of the unit
  • Low ambient operation across classes

Feature Icons

Economy mode: A thermostat setting is adjusted automatically according to the room temperature to avoid unnecessary cooling or heating. Auto changeover: The unit automatically switches between heating and cooling modes based on the temperature setting and the room temperature. Automatic fan speed: A micro-computer automatically adjusts the airflow to follow the changes in room temperature. Auto restart: In the event of a temporary power failure, the air conditioner will automatically restart in the same operating mode as before, once the power supply is restored. Connectable fresh air duct: Outside air can be introduced by attaching a locally purchased duct to the fresh air knockout and an optional part. Connectable distributing duct: Locally purchased branch ducts can be attached to the systems to distribute the airflow. Weekly & Temperature setback timer: Weekly & Temperature setback timer can set the temperature for 2-time spans and for each day of the week. Filter sign: Indicates the filter cleaning period by blinking. Blue fin

Capacity

Cooling   9.5 kW
Heating   10.8 kW


Specifications

Power Source Phase 3 phase 3N
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 9.5 (2.8 - 11.2) kW
Heating 10.8 (2.7 - 12.7) kW
Input Power Cooling 2.970 kW
Heating 2.880 kW
EER Cooling 3.20 W/W
COP Heating 3.75 W/W
Pdesign Cooling 9.5 kW
Heating (-10°C) 8.7 kW
SEER Cooling 6.10 W/W
SCOP Heating (Average) 4.00 W/W
Energy Efficiency Class Cooling A++
Heating (Average) A+
Max. Operating Current Cooling 10.5 A
Heating 10.5 A
Annual Energy Consumption Cooling 545 kWh/a
Heating 3044 kWh/a
Moisture Removal 3.0 l/h
Sound Pressure Level*2 Indoor (Cooling) High 39 dB(A)
Middle 35 dB(A)
Low 30 dB(A)
Quiet 26 dB(A)
Indoor (Heating) High 42 dB(A)
Middle 35 dB(A)
Low 30 dB(A)
Quiet 26 dB(A)
Sound Pressure Level*2 Outdoor (Cooling) High 55 dB(A)
Outdoor (Heating) High 55 dB(A)
Sound Power Level Indoor (Cooling) High 65 dB(A)
Indoor (Heating) High 70 dB(A)
Outdoor (Cooling) High 70 dB(A)
Outdoor (Heating) High 70 dB(A)
Airflow Rate Indoor (Cooling) High 1900 m³/h
Outdoor (Cooling) High 3750 m³/h
Static Pressure Range (standard) 30 - 150 (47) Pa
Net Dimensions
Indoor
Height 270 mm
Width 1135 mm
Depth 700 mm
Net Dimensions
Outdoor
Height 788 mm
Width 940 mm
Depth 320 mm
Net Weight Indoor 38.0 kg
Outdoor 53 kg
Connection Pipe Diameter Liquid φ9.52 mm
Gas φ15.88 mm
Max. Pipe Length (Pre Charge) 50 (30.0) m
Max. Height Difference 30 m
Operation Range Cooling -15 to 46 °C DB
Heating -15 to 24 °C DB
Refrigerant Type R32
Global Warming Potential 675
Charge 1900 g (1.283 CO2eq–T)
Scroll

Dimensions

Indoor Unit : ARXG36KMLA

Indoor unit