Cassette Compact 4-way Flow Series (Compact Size) AUXG18KVLA

Indoor unit, remote controller, outdoor unit

All DC V-PAM
Indoor Unit :
AUXG18KVLA
Outdoor Unit :
AOHG18KBTB
Download :
Catalogues

Features

  • Compact and stylish panel design
  • Easy maintenance
  • Flexible installation
  • Low ambient operation

Feature Icons

Economy mode: A thermostat setting is adjusted automatically according to the room temperature to avoid unnecessary cooling or heating. 10ºC heating operation: The room temperature can be set to not go below 10°C so that the room will not become too cold when unoccupied. Auto changeover: The unit automatically switches between heating and cooling modes based on the temperature setting and the room temperature. Vertical swing louver: The louver automatically swings up and down. Automatic fan speed: A micro-computer automatically adjusts the airflow to follow the changes in room temperature. Auto restart: In the event of a temporary power failure, the air conditioner will automatically restart in the same operating mode as before, once the power supply is restored. Sleep timer: A micro-computer gradually changes the room temperature automatically to promote a comfortable night's sleep. Program timer: This digital timer allows selection of one of four options: ON, OFF, ON » OFF, or OFF » ON. Drain pump equipped as standard

Capacity

Cooling   5.2 kW
Heating   6.0 kW


Specifications

Power Source Phase Single phase
Voltage 230 V
Frequency 50 Hz
Capacity Cooling 5.2 (0.9 - 5.9) kW
Heating 6.0 (0.9 - 7.5) kW
Input Power Cooling 1.600 kW
Heating 1.660 kW
EER Cooling 3.25 W/W
COP Heating 3.61 W/W
Pdesign Cooling 5.2 kW
Heating (-10°C) 4.4 kW
SEER Cooling 6.60 W/W
SCOP Heating (Average) 4.20 W/W
Energy Efficiency Class Cooling A++
Heating (Average) A+
Max. Operating Current Cooling 12.10 A
Heating 12.10 A
Annual Energy Consumption Cooling 275 kWh/a
Heating 1466 kWh/a
Moisture Removal 2.20 l/h
Sound Pressure Level*2 Indoor (Cooling) High 38 dB(A)
Middle 34 dB(A)
Low 30 dB(A)
Quiet 26 dB(A)
Indoor (Heating) High 43 dB(A)
Middle 38 dB(A)
Low 34 dB(A)
Quiet 30 dB(A)
Sound Pressure Level*2 Outdoor (Cooling) High 50 dB(A)
Outdoor (Heating) High 50 dB(A)
Sound Power Level Indoor (Cooling) High 50 dB(A)
Indoor (Heating) High 55 dB(A)
Outdoor (Cooling) High 62 dB(A)
Outdoor (Heating) High 62 dB(A)
Airflow Rate Indoor (Cooling) High 680 m³/h
Outdoor (Cooling) High 2160 m³/h
Net Dimensions
Indoor
Height 245 mm
Width 570 mm
Depth 570 mm
Net Dimensions
Outdoor
Height 632 mm
Width 799 mm
Depth 290 mm
Net Weight Indoor 15.0 kg
Outdoor 36.0 kg
Connection Pipe Diameter Liquid φ6.35 mm
Gas φ12.7 mm
Drain Hose Diameter φ25(I.D.), φ32(O.D.) mm
Max. Pipe Length (Pre Charge) 30.0 (20.0) m
Max. Height Difference 20 m
Operation Range Cooling -15 to 46 °C DB
Heating -15 to 24 °C DB
Refrigerant Type R32
Global Warming Potential 675
Charge 1020 g (0.689 CO2eq–T)
Scroll

Dimensions

Indoor Unit : AUXG18KVLA

Indoor unit