Capacity

Cooling  113.5 kW
Heating  127.5 kW


Specifications

Rated Capacity Range 40
Max. Number of Connectable Indoor Units*1 64
Connectable Capacity of Indoor Units 56.8 - 170.2 kW
Scroll
Power Source Phase 3 phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 113.5 kW
Heating 127.5 kW
Input Power Cooling 30.88 kW
Heating 30.99 kW
EER Cooling 3.68 W/W
COP Heating 4.11 W/W
Airflow Rate 13,000×3 m³/h
Sound Pressure Level*2 Cooling 64 dB(A)
Heating 66 dB(A)
Sound Power Level Cooling 85 dB(A)
Heating 88 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 11.0×3 kW
Heat Exchanger Fin Blue fin
Net Dimensions Height 1,690 mm
Width 1,240×3 mm
Depth 765 mm
Net Weight 275×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.8×3 kg
Connection Pipe Diameter Liquid 19.05 mm
Gas 41.27 mm
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are subject to the following conditions:
Cooling:
Indoor temperature of 27°C DB/19°C WB; outdoor temperature of 35°C DB/24°C WB
Heating:
Indoor temperature of 20°C DB/(15°C WB); outdoor temperature of 7°C DB/6°C WB
Pipe length:
7.5 m Height difference between outdoor unit and indoor unit: 0 m
When cooling operation will be conducted at outdoor air temperature below -5°C,
the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,