Heat Pump Modular Type V-III Series AJH234LALBHH

Outdoor unit

Outdoor Unit :
AJH090LALBH
Outdoor Unit :
AJH072LALBH
Outdoor Unit :
AJH072LALBH
Download :
Catalogues

Features

  • Excellent energy saving
  • Great design flexibility for placement in any building
  • Easy installation and maintenance
  • Outstanding efficiency in real-world operating conditions
  • Energy-saving technologies for boosting operational efficiency

Capacity

Cooling  72.8 kW
Heating  81.5 kW


Specifications

Rated Capacity Range 26
Max. Number of Connectable Indoor Units*1 56
Connectable Capacity of Indoor Units 36.4 - 109.2 kW
Scroll
Power Source Phase 3 phase 4 wire
Voltage 400 V
Frequency 50 Hz
Capacity Cooling 72.8 kW
Heating 81.5 kW
Input Power Cooling 17.68 kW
Heating 17.59 kW
EER Cooling 4.12 W/W
COP Heating 4.63 W/W
Airflow Rate 11,000×3 m³/h
Sound Pressure Level*2 Cooling 62 dB(A)
Heating 63 dB(A)
Sound Power Level Cooling 83 dB(A)
Heating 85 dB(A)
Max. External Static Pressure 82 Pa
Compressor Motor Output 7.5×3 kW
Heat Exchanger Fin Blue fin
Net Dimensions Height 1,690 mm
Width 930×3 mm
Depth 765 mm
Net Weight 252×3 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 11.7×3 kg
Connection Pipe Diameter Liquid 15.88 mm
Gas 34.92 mm
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are subject to the following conditions:
Cooling:
Indoor temperature of 27°C DB/19°C WB; outdoor temperature of 35°C DB/24°C WB
Heating:
Indoor temperature of 20°C DB/(15°C WB); outdoor temperature of 7°C DB/6°C WB
Pipe length:
7.5 m Height difference between outdoor unit and indoor unit: 0 m
When cooling operation will be conducted at outdoor air temperature below -5°C,
the outdoor unit must be installed in a position that is higher than or equal to those of indoor units.
*1
Minimum connectable indoor unit number is 2.
*2
The noise value is the value when measured in an anechoic room. When measured in the actual installed state,
surrounding noise and reflections are received and the measured value is usually larger than the indicated value.

Dimensions

Outdoor Unit : AJH090LALBH / AJH072LALBH / AJH072LALBH

Outdoor unit