Heat Pump for Small Capacity Type J-IIIL Series AJH162LELAH
Features
- Compact design
- Advanced technologies for high efficiency
- Long piping length
- Top class indoor unit connection
- High static pressure
- Best-in-class low-noise operation
Capacity
50.0 kW
50.0 kW
Specifications
Rated Capacity Range | 18 |
---|---|
Max. Number of Connectable Indoor Units*1 | 1 - 42 |
Scroll
Power Source | Phase | 3 phase |
---|---|---|
Voltage | ~400 V | |
Frequency | 50 Hz | |
Capacity | Cooling | 50.0 kW |
Heating | 50.0 kW | |
Input Power | Cooling | 18.52 kW |
Heating | 13.66 kW | |
EER | Cooling | 2.70 W/W |
COP | Heating | 3.66 W/W |
Airflow Rate | 14,800 m³/h | |
Sound Pressure Level*2 | Cooling | 65 dB(A) |
Heating | 68 dB(A) | |
Net Dimensions | Height | 1,638 mm |
Width | 1,080 mm | |
Depth | 480 mm | |
Net Weight | 217 kg | |
Refrigerant | Type | R410A |
Charge | 11.8 kg | |
Connection Pipe Diameter | Liquid | 12.70 mm |
Gas | 28.58 mm | |
Total Pipe Length | 400 m | |
Max. Height Difference |
50 m
40 m |
|
Operation Range | Cooling | -5 to 46 °CDB |
Heating | -20 to 21 °CDB |
Scroll
- Note:
- Specifications are subject to the following conditions:
- Cooling:
- Indoor temperature of 27°C DB/19°C WB; outdoor temperature of 35°C DB/24°C WB
- Heating:
- Indoor temperature of 20°C DB/(15°C WB); outdoor temperature of 7°C DB/6°C WB
- *
- The cooling operation range of -15 to 46°C is allowed only when all of the indoor units connected to the system are higher than capacity of 5.6kW.
- Pipe length:
- 7.5 m Height difference between outdoor unit and indoor unit: 0 m