Heat Pump for Small Capacity Type J-IIS Series AJH040LCLAH

Outdoor unit

Outdoor Unit :
AJH040LCLAH
Download :
Catalogues

Features

  • Small and lightweight outdoor units
  • Advanced technologies for high efficiency
  • Long piping length
  • Nonstop operation during oil recovery
  • Easy installation

Capacity

Cooling  12.1 kW
Heating  13.6 kW


Specifications

Rated Capacity Range 4
Max. Number of Connectable Indoor Units*1 7
Scroll
Power Source Phase Single phase
Voltage ~230 V
Frequency 50 Hz
Capacity Cooling 12.1 kW
Heating 13.6 kW
Input Power Cooling 3.44 kW
Heating 3.09 kW
EER Cooling 3.52 W/W
COP Heating 4.40 W/W
Airflow Rate 4,040 m³/h
Sound Pressure Level*2 Cooling 51 dB(A)
Heating 54 dB(A)
Sound Power Level Cooling 67 dB(A)
Heating 68 dB(A)
Heat Exchanger Fin Blue fin
Net Dimensions Height 998 mm
Width 970 mm
Depth 370 mm
Net Weight 86 kg
Refrigerant Type R410A
Global Warming Potential 2,088
Charge 4.0 kg
Connection Pipe Diameter Liquid 9.52 mm
Gas 15.88 mm
Total Pipe Length 80 m
Max. Height Difference 30 m
Operation Range Cooling -5 to 46 °CDB
Heating -20 to 21 °CDB
Scroll
Note:
Specifications are subject to the following conditions:
Cooling:
Indoor temperature of 27°C DB/19°C WB; outdoor temperature of 35°C DB/24°C WB
Heating:
Indoor temperature of 20°C DB/(15°C WB); outdoor temperature of 7°C DB/6°C WB
Pipe length:
7.5 m Height difference between outdoor unit and indoor unit: 0 m
The protective function may work when using it outside the operation range.

Dimensions

Outdoor Unit : AJH040LCLAH

Outdoor unit